Data centre Munich

Basic data about the data centre
  • First-Class Data centre
  • Munich, Germany
  • 20.350 m2 fenced ground
  • 15.525 m2 building floor size
  • 9.638 m2 available area for servers
  • 20 compartments (expandable)
  • 5.120 KW high available electric/cooling, expandable to 10 MW, Redundancy: n+1
  • Network provider:
    • COLT (redundancy via M-net)
    • Deutsche Telekom (own redundant ring connection)
    • M-net (own redundant ring connection)
  • Certifications:
    • ISO 9001
    • BS 7799



Safety - our data centre’s security infrastructure meets the demands of today and tomorrow
  • free-standing building
  • not shared between companies
  • inconspicuously located in the Euroindustriepark
  • constructed completely of concrete and steel
  • groundwater table is 14 meters below surface
  • building is 1,3 meters above the canalisation
  • special roof with 300 leakage detection tiles
  • central sanitation and meeting rooms
  • thunder protection

  • 2,9 meter high fence with perimeter surveillance
  • steel barricades at entry point to block vehicles
  • road blocker with water gate
  • camera surveillance
  • vehicle and identification card control system



The implementation of the guidelines is our top priority
  • metal detector
  • isolation room
  • 24x365/366 Security
  • access per chip card
  • cctv video
  • motion sensor, infrared sensor, light sensor

  • dual independent fire alarm systems
  • early fire detection system (VESDA)
  • fire retardant doors and walls (F90)
  • argon fire suppression system (300 bottles)
  • direct connection to the fire department

  • 60 centimeter raised floor
  • raised floor capacity: 3 metric tons
  • single point capacity: 500kg
  • emergency plans, handbooks and professional building maintenance and management
  • 24 hours on call service



Power system - we place most value and care on uninterrupted power flow to your equipment
  • 5 direct feeds from the city
  • separate MSHV (10,000 V level)
  • 5 transformers
  • separate NSHV (400 V level)
  • AC 230 V or DC 400 V

  • redundant spare network (NEA)
  • Diesel supply of 240.000 Liter for 72 hours full power operation
  • redundant no-break current supply, also statically over 1,200 batteries
  • grounded according to telecommunications standards

  • separate A-/B-/C-Power Rail system for both critical and noncritical equipment
  • each co-location space has its own rail system
  • separate Power Distribution Unit for A-, B- and C- customer assignment



Air Conditioning - your high power equipment requires only the best in air conditioning
  • redundant coldwater chillers with automatic switch
  • air circulation in raised floor
  • master/slave control
  • air temperature: 24 ±4°C
  • Humidity: 45% ±10%

  • central humidity outside of server area
  • redundant pipe system
  • central intake and exhaust air pipes
  • two-step air filtering (dirt and dust)
  • complete air exchange in 2 hours